The Simplicity Plus 252 has user definable zones, option for zonal or common alarm operation, options for I/O operation, alarm verification and user selectable languages. It can be connected to an RS232 desktop printer for real time event log printing (Epson LQ300+ recommended) and it can also drive a serial repeater model AD-REP.
Features:
- Two loop addressable fire alarm panel (252 device capacity)
- Complies fully to EN54 parts 2 & 4
- User definable zones
- Option for zonal or common alarm operation
- Options for I/O operation
- Alarm verification (help prevent false alarms)
- User selectable languages
- Set of changeover relay contacts for fault condition
- Set of changeover relay contacts for fire condition
- 2,048 event log (fire & fault)
- Zone or device disablement
- One man test mode
- Plug & play, no need for any special tools or laptop for commissioning
- Fully integrated Qwerty keypad
- All associated devices are loop powered
Specification:
- Supply Voltage: 230V AC +/- 10%
- System Voltage: 24V DC (Nominal)
- Number Of Loop: 2
- Loop Capacity: 126 devices per loop (Total 252)
- Number Of Zones: 8
- Sounder Output: Addressable Sounders Only
- Fault Output: 28V Repeat Output To Drive Relay (Normally Energised)
- Fire Output: 28V Repeat Output To Drive Relay
- Operating Temperature: -0°C to 50°C
- Enclosure Size: 375 X 335 X 125mm
- Weight: 4.0 KG
Additional Information
Model |
SP-252/M |
Suggested Use |
Commercial |
Manufacturer |
Zeta |
Connections |
Analogue Addressable |